Fault Diagnosis of Low-Power Three-Phase Induction Motor
2016
Gedzurs, Aleksejs
An Induction motor reliability survey at an egg processing plant shows that almost 50% of the total motor failures are fan induction motors. Visual investigations of the faulty fan motors show that the main cause of the induction motor failure is air gap eccentricity. In this study, experimental tests are performed on a 1.1kW three-phase induction motor to detect air gap eccentricity and overheating of the induction motor. Heating tests show that end shield housing temperature reaches 100°C with blocked air flow from the fan, which can reduce the lifespan of the bearing. Dimension measurements of the end shield housing show that the dimensions of both tested motors back-end shields are larger than ISO tolerance grade limit. It leads to a loose fit between the housing and bearing, causing air gap eccentricity. Also, both motor back end shield housing has an out-of-round condition leading to an unbalanced magnetic pull. To detect the air gap eccentricity caused by too loose of a fit between housing bore and bearing, current Park’s vector approach is used. To measure three phase current, Hall Effect current transducers, a digital oscilloscope is used and Matlab software to process the measurement data. Results show that Park’s vector approach can be used to detect the air gap eccentricity caused by too loose a fit between bearing and housing. Therefore, the Park’s vector approach can be used to diagnose air gap eccentricity and analyse the type of the air gap eccentricity.