Filter Backwash Water and Floated Residue Containing Pathogenic Protozoa: Detection Method and Treatment Alternatives
2020
Silva, Hugo Guilherme | Sabogal-Paz, Lyda Patricia
Treatments using ozone for filter backwash water (FBW) and calcium oxide for floated residue (FR) were evaluated adopting bench-scale testing for the inactivation of Giardia spp. cysts and Cryptosporidium parvum oocysts. The protocol chosen for protozoa detection involved following the concentration step by direct centrifugation (adding ICN 7X cleaning solution at 1.0%) and purification by immunomagnetic separation (IMS). The FR treatment with calcium oxide (dosage of 23 mg CaO 100 mL⁻¹ and 3-day contact time at 25 °C) proved to be efficient, as no parasites were detected after the treatment. The reduction of calcium oxide dosage (16 mg CaO 100 mL⁻¹ and 3-day contact time at 25 °C) was insufficient to inactivate the protozoa, since potentially viable organisms were identified using propidium iodide (PI). Concerning the disinfection conditions with ozone (5-min and 10-min contact time and dosage of 10 mg O₃ L⁻¹ and 7.5 mg O₃ L⁻¹, respectively), there was complete removal of the target organisms, as no protozoa were detected after the FBW treatment. From the results obtained, the tested treatments can be considered promising alternatives for water treatment plants (WTPs). However, the costs incurred from these treatments have to be considered.